| Specifiche |
Valore |
| Modello |
ZX11-1K-BAT24V |
| Capacità |
1000VA/800W |
| Efficiency – utility mode / battery mode |
88% / 83% |
| Number of batteries |
2 |
| Charging voltage |
27.3 VDC +/-1% |
| Dimensions, D x W x H – tower / rack |
316 x 146 x 216.5 mm / 482 x 87 x 420 mm |
| Net weight – tower / rack |
7 kg / 11.5 kg |
| Input voltage range – low transfer voltage |
160/140/120/110 VAC +/-5% (ambient temperature below 35 C), according to load ratio 100%-80% / 80%-70% / 70%-60% / 60%-0% |
| Input voltage range – low recovery voltage |
175/155/135/125 VAC +/-5% (ambient temperature below 35 C), according to load ratio 100%-80% / 80%-70% / 70%-60% / 60%-0% |
| High transfer / recovery voltage |
300 VAC / 290 VAC (as stated in source: 5%) |
| Input frequency range |
40-70 Hz |
| Fase |
Single-phase, grounded |
| Fattore di potenza |
>= 0.99 at 220-230 VAC input |
| Tensione di uscita |
200/208/220/230/240 VAC |
| Output voltage regulation (battery mode) |
+/-1% |
| Frequency range – synchronized |
47-53 Hz or 57-63 Hz |
| Frequency range – battery mode |
50 Hz +/-0.25 Hz or 60 Hz +/-0.3 Hz |
| Overload (ambient temperature below 35 C) |
105%-110%: shuts down after 10 minutes in battery mode or switches to bypass when input is normal. 110%-130%: shuts down after 1 minute in battery mode or switches to bypass when input is normal. >130%: shuts down after 3 seconds in battery mode. |
| Crest factor |
3:1 |
| Distorsione armonica |
<=3% THD (linear load); <=5% THD (non-linear load) |
| Transfer time |
Utility mode to battery mode: zero; frequency-conversion mode to bypass: 4 ms (under standard conditions) |
| Waveform (battery mode) |
Pure sine wave |
| Battery specification |
12 VDC per battery. K models: built-in 7 Ah or 9 Ah batteries. KS models: external batteries according to customer requirements. |
| Charging current |
K model: 1 A. KS models: 1 A / 2 A / 4 A / 6 A. |
| Operating humidity |
20%-90% RH at 0-40 C, non-condensing |
| Rumore |
Less than 50 dBA at 1 m |
| Management – RS-232 or USB |
Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, Unix, and Mac |
| SNMP compatibility |
Supports power management by an SNMP manager and web browser |
| Special notes |
(1) Capacity is derated to 80% in frequency-conversion mode and when output voltage is set to 200 VAC or 208 VAC. (2) Product specifications are subject to change without notice. |