جدول المحتويات إخفاء

Wiring an محول العزل correctly is essential for safety, EMC performance and reliable operation of downstream equipment. This guide walks you through practical, standards-aware steps—what to check before you wire, how to make common single-phase and three-phase connections, and which tests and safety precautions to perform. Always have a qualified electrician or technician carry out the work and follow local electrical codes.

What-is-Isolation-Transformer

Before you start — safety & verification

  1. De-energize, lockout/tagout and verify zero voltage. Never work on live primary/secondary terminals.
  2. Read the nameplate & datasheet. Confirm primary/secondary voltages, kVA, vector group, insulation class, rated current and terminal identification.
  3. Check the installation environment. Adequate ventilation, clearance, ambient temp and altitude limits per datasheet.
  4. Gather tools & PPE. Calibrated meter, megger, TTR (turns-ratio) tester (if available), torque wrench, correct-rated lugs, insulating gloves, eye protection.
  5. Select correct cabling & protective devices. Cable gauge, breakers/fuses and protective relays sized for rated current and inrush characteristics.

Single-phase isolation transformer — common wiring (step-by-step)

Typical use: 230 V → 230 V 1:1 isolation, or step-down/up single-phase loads.

  1. Identify terminals. Primary terminals typically labeled H1 / H2 (or L / N). Secondary labeled X1 / X2 (or L’ / N’). Earth/Shield terminal labelled PE or “Shield”.
  2. Connect primary supply. Connect live (L) to H1 and neutral (N) to H2 according to the nameplate. Tighten terminals to manufacturer torque.
  3. Connect protective earth. Bond the transformer frame and dedicated PE terminal to site protective earth. If an electrostatic shield is present, connect its drain terminal to earth per manufacturer instructions.
  4. Connect secondary load. Connect load live to X1 and neutral to X2. If the transformer is 1:1 for isolation, you may choose to leave the secondary ungrounded (floating) for maximum isolation, or ground the secondary neutral if a solid neutral is required by the installation—only as dictated by the application and local code.
  5. Install overcurrent protection. Place fuses or breakers on the primary side sized per transformer’s rated primary current; consider secondary protection where applicable.
  6. Verify wiring. Continuity check (de-energized): confirm no continuity primary↔secondary. Megger test per datasheet if needed. TTR confirms ratio.

Important: Do not create parallel neutral/earth ties on the secondary without consulting the system design—doing so can defeat isolation and create ground loops.

Three-phase isolation transformer — common connection modes & wiring notes

Three-phase isolation transformers are often wired in Y (star) أو Δ (delta) configurations and can be connected as Y-Y, Y-Δ, Δ-Y, etc. Your choice affects phase shift (vector group) and whether a neutral is available.

  1. Confirm vector group (clock notation). Nameplate will show e.g., Dyn11, Yyn0. This defines the phase relationship between primary and secondary and whether a neutral is brought out. Never mix phases with mismatched vector groups—this causes circulating currents and damage.
  2. Wiring examples:
    • Y-Y with neutral (Yyn0): Primary phases to H1/H2/H3, primary neutral to Hn. Secondary phases to X1/X2/X3, secondary neutral Xn grounded if required. Good when neutral required on both sides and no phase shift.
    • Δ-Y (D-y) step-down with neutral on secondary (Dyn11): Primary delta (no neutral), secondary star with neutral available—commonly used to create a grounded neutral on secondary.
  3. Grounding & shields: If electrostatic shield (screen) exists, connect the shield to earth only, per manufacturer instructions—this suppresses common-mode interference while maintaining galvanic isolation.
  4. Sequential wiring & phasing: When connecting, ensure proper phase sequence. Use a phase rotation tester to confirm correct orientation before energizing.

Tests & commissioning (de-energized & energized)

  • Continuity check (de-energized): primary-to-secondary should read open.
  • Insulation resistance (megger): verify MΩ between windings and to earth per datasheet.
  • Turns-ratio test (TTR): confirm correct turns ratio and detect shorted turns.
  • Hi-pot (dielectric) test: only by qualified personnel following standards if required.
  • No-load energize & monitor: energize with no load; measure voltages, neutral/earth voltages, and look for unexpected heating or sound.
  • Load test: apply expected load and verify temperature rise, regulation and protection trip settings.

Best practices & installation tips

  • Use correct torque on all terminal connections to avoid overheating.
  • Provide clear labels for primary/secondary terminals and grounding points.
  • Keep primary and secondary conductors physically separated to reduce induced coupling and ease maintenance.
  • For noise-sensitive equipment, use a transformer with an electrostatic shield and follow grounding instructions carefully.
  • Keep manufacturer’s wiring diagrams and factory test reports with the unit.

Compliance & responsibility

Always follow local electrical codes (IEC, NEC, or regional equivalents), manufacturer installation manual, and site earthing rules. If the transformer powers medical, laboratory, or safety-critical systems, insist on factory test certificates and certified installers.

الأسئلة الشائعة

Q1 — Should I ground the secondary of an isolation transformer?
It depends. Leaving the secondary floating maximizes galvanic isolation but may complicate protective earth strategies. If a neutral is required for protective devices or equipment, ground the secondary neutral per local code and manufacturer guidance.

Q2 — How do I avoid phase shift or circulating currents in three-phase installations?
Match the transformer’s vector group exactly to system requirements. Never parallel transformers with different vector groups. Use correct delta/star connections and confirm phase rotation before energizing.

Q3 — Who should perform hi-pot and TTR tests?
Only trained, authorized technicians should perform hi-pot and TTR testing. These tests require proper safety procedures and calibrated equipment; improper testing can damage insulation or create hazards.

Related Blogs

Related Products

محول التحكم في الإضاءة المحمول أحادي الطور JMB محول التحكم في الإضاءة المتنقل أحادي الطور 25 فولت أمبير ~ 50 كيلو فولت أمبير

سلسلة JMB عبارة عن محول التحكم أحادي الطور المتين والمحمول أحادي الطور المصمم للإضاءة والمعدات الصناعية الصغيرة. وهي تقوم بتخفيض جهد التيار الكهربائي العادي إلى مخرجات معزولة ذات جهد إضافي منخفض للسلامة (SELV) - مثالية لمواقع العمل الرطبة والأماكن الضيقة والحاويات المعدنية حيث تكون السلامة مهمة. متوفرة من 25 فولت أمبير حتى 50 كيلو فولت أمبير، مع صنابير متعددة وميزات حماية اختيارية.

محول تحكم عالي الكفاءة 500 فولت أمبير - 1000 كيلو فولت أمبير ثلاثي الأطوار من النوع الجاف 415 فولت 400 فولت 380 فولت

يوفر محول التحكم الجاف ثلاثي الأطوار من النوع الجاف من سلسلة SBK (500VA-1kVA) تحويل جهد مدمج وموثوق به لتطبيقات التحكم الصناعي والأتمتة والآلات. متوفر بجهد أولي وثانوي قابل للتكوين (قياسي: 380 فولت / 400 فولت / 415 فولت) ومصمم لأنظمة 50 هرتز أو 60 هرتز، وهذا المحول مصمم لشبكات الجهد المنخفض (<1 كيلو فولت). يزيل هيكله الجاف والمبرد بالهواء الزيت ويقلل من مخاطر الحريق ويقلل من الصيانة الروتينية - مما يجعله خيارًا آمنًا وفعالًا من حيث التكلفة لمراكز التحكم في المحركات وأنظمة التحكم الرقمي باستخدام الحاسوب وخزانات PLC ولوحات التوزيع.

محول عزل متوازن أحادي الطور GBK2 أحادي الطور من 220 فولت إلى 220 فولت حلقية متوازنة 300 فولت - 2 كيلو فولت أمبير

اضمن جودة طاقة نقية وأقصى درجات الأمان للأحمال الحساسة باستخدام محول العزل الحلقي GBK2. صُممت سلسلة GBK2 للتطبيقات التي تتطلب ضوضاء منخفضة وتسربًا منخفضًا وإخراجًا مستقرًا (220 فولت ← 220 فولت)، وهي تعزل معداتك عن اضطرابات التيار الكهربائي وتمنع العابرين وتقلل من تداخل الوضع الشائع. ويوفر قلبه الحلقي المدمج كفاءة أعلى وطنينًا مسموعًا أقل من المحولات المغلفة التقليدية - وهو مثالي ل الأجهزة الطبية والأجهزة الصوتية الاحترافية والأدوات المعملية وأجهزة التحكم الصناعية.

JBK 25 فولت أمبير - 5000 فولت أمبير محول عزل من النوع الجاف أحادي الطور للتحكم في الماكينة من 220 فولت إلى 110 فولت

إن سلسلة JBK هو نوع جاف مضغوط من النوع الجاف محول التحكم مصممة للتحكم في الماكينة وعزلها في اللوحات الصناعية. الاستخدام النموذجي هو 220 فولت → 110 فولت دارات تحكم للموصلات والمرحلات وأجهزة التحكم المنطقية القابلة للبرمجة وأجهزة الاستشعار. صُممت JBK لتوفر ضوضاء منخفضة وموثوقية عالية وسهولة التركيب في الخزانة، وتحمي دوائر التحكم من اضطرابات التيار الكهربائي مع تبسيط الأسلاك والصيانة.