Un transformateur d'isolement provides galvanic separation between its primary and secondary windings. That electrical separation improves safety, reduces common-mode noise and ground-loop interference, and protects sensitive equipment. Before installation, testing, or procurement, it’s important to be able to confirm that a unit is a true isolation transformer — not an autotransformer or a different control transformer. This guide gives field-tested, safety-first steps and the documentation you should demand from suppliers.
1. Check the nameplate and datasheet first
The quickest, non-intrusive check is the transformer nameplate and accompanying datasheet. Look for clear indicators:
Primary and secondary voltages (e.g., 230 V : 230 V) and kVA rating.
Explicit wording like “Isolation Transformer”, “Isolating”, or a 1:1 specification when isolation is the unit’s purpose.
Vector group or connection diagram and insulation class (F/H).
Factory test references (hi-pot, insulation resistance) listed or available on request.
A nameplate alone isn’t definitive, but it’s the first and required piece of evidence.
2. Visual & wiring clues on the unit
Isolation transformers typically have separate, clearly labelled terminal blocks for primary and secondary. Additional signs: a dedicated shield/earth terminal (for electrostatic screens), separate enclosure compartments, and robust insulation barriers. If terminals are tied together or share the same block, treat that unit with suspicion.
Important: always disconnect power and apply lockout/tagout before testing.
Using a digital multimeter in ohms mode, check for continuity between any primary terminal and any secondary terminal. For a genuine isolation transformer you should read no continuity (open circuit). A low resistance reading means the windings are directly connected — that unit is not isolated.
4. Insulation resistance (megger) test — field verification
An insulation-resistance (megger) test measures how well primary and secondary are isolated. Measure MΩ between primary and secondary and between each winding and earth. Acceptable values are typically in the megaohm range; compare to the manufacturer’s datasheet. Low insulation resistance indicates compromised inter-winding insulation.
5. Turns-ratio test (TTR) — confirms winding correctness
A Transformer Turns Ratio tester verifies the expected ratio between primary and secondary. For 1:1 isolation transformers the TTR should read near 1.0. Significant deviations can indicate shorted turns, incorrect wiring, or manufacturing faults.
6. Hi-pot (dielectric) test — definitive proof (trained personnel only)
High-potential testing applies a controlled high AC or DC voltage between primary and secondary to validate insulation strength. This test must be performed by trained technicians following standards (IEC/UL/local codes). Do pas hi-pot on site without proper procedures — it can stress insulation if done incorrectly.
7. Ask for documented evidence (EEAT checklist)
To prove isolation performance and support procurement decisions, request:
Factory hi-pot and insulation test reports.
TTR and temperature-rise test reports.
Compliance certificates (IEC/UL/CE as required).
Wiring diagrams and installation instructions.
Buyer’s quick checklist (one view)
Nameplate: labelled “Isolation” or 1:1 spec ✔
Separate primary & secondary terminals ✔
Continuity test: no primary-to-secondary continuity ✔
Megger: MΩ per datasheet ✔
TTR: expected ratio ✔
Factory hi-pot & test reports ✔
FAQ
Q1 — Can a 1:1 transformer still NOT be an isolation transformer? Yes. 1:1 ratio indicates equal voltages but does not guarantee separate windings. Always confirm separation via terminal layout, continuity and test reports.
Q2 — Is a megger test enough to prove isolation? A megger is a strong field test but should be combined with TTR and hi-pot (when needed) plus factory reports for full assurance.
Q3 — Who should perform hi-pot and TTR tests? Only trained technicians or authorized service engineers should perform hi-pot or TTR tests, following safety procedures and standards.
Need verified isolation transformers with factory test reports and on-site commissioning? Contact ZHENGXI Technical Support for datasheets and certified test documentation.
La série JMB est notre transformateur de contrôle monophasé robuste et portable, conçu pour l'éclairage et les petits équipements industriels. Il abaisse les tensions secteur courantes vers des sorties isolées à très basse tension de sécurité (TBTS), idéales pour les chantiers humides, les espaces confinés et les enceintes métalliques où la sécurité est primordiale. Disponible de 25 VA à 50 kVA, avec plusieurs prises et fonctions de protection en option.
Le transformateur de contrôle triphasé sec de la série SBK (500 VA–1 kVA) offre une conversion de tension compacte et fiable pour les applications de contrôle industriel, d'automatisation et de machines. Disponible avec des tensions primaires et secondaires configurables (standard : 380 V / 400 V / 415 V) et homologué pour les systèmes à 50 Hz ou 60 Hz, ce transformateur est conçu pour les réseaux basse tension (< 1 kV). Sa conception sèche et refroidie par air élimine l'huile, réduit les risques d'incendie et simplifie la maintenance, ce qui en fait un choix sûr et économique pour les centres de contrôle moteur, les systèmes CNC, les armoires d'automates programmables et les tableaux de distribution.
Assurez une qualité d'énergie irréprochable et une sécurité maximale pour les charges sensibles avec le Transformateur d'isolement toroïdal GBK2. Conçue pour les applications exigeant un faible bruit, de faibles fuites et une sortie stable (220 V → 220 V), la série GBK2 isole vos équipements des perturbations du secteur, supprime les transitoires et réduit les interférences de mode commun. Son noyau toroïdal compact offre un rendement supérieur et un ronflement audible plus faible que les transformateurs feuilletés classiques, ce qui en fait la solution idéale. dispositifs médicaux, audio professionnel, instruments de laboratoire et contrôles industriels.
Le Série JBK est un type sec compact transformateur de commande Conçu pour le contrôle et l'isolation des machines dans les tableaux industriels. Utilisations courantes : 220 V → 110 V Circuits de commande pour contacteurs, relais, automates programmables et capteurs. Conçus pour un faible bruit, une grande fiabilité et un montage facile en armoire, les circuits JBK protègent les circuits de commande des perturbations du secteur tout en simplifiant le câblage et la maintenance.
Nous utilisons des cookies pour améliorer votre expérience sur notre site web. En naviguant sur ce site, vous acceptez que nous utilisions des cookies.